Page 45 - ParkerMULTITUBE

SEO Version

42
Parker Hannifn Corporation
Parfex Division
Ravenna, OH
Process Control & Analyzer Systems
Catalog Number 4200-M-2
Heater type
4 W./ft.
11.4W./ft.
Insulation
PFA Tefon® 600 V rated
PFA Tefon
®
600V rated
Bus wire size
12 AWG
12 AWG
Heating zone length**
18" (45.7 cm) and 24" (61 cm)
**Installation Note:
Caution:
Cutting beyond heating zone
indentation will result in an unheated
section of the heater wire for the balance
of the heating zone length. The bus wires
MUST NOT be connected together on the
termination end!
Part
Number
Series
Power Consumption
W/ft (W/m)
Voltage Maximum Circuit
Length*** ft (m)
Current A/ft (A/m)
CL
4
(13.1)
120
340
(103.6)
0.033
(0.108)
240
680
(207.3)
0.017
(0.55)
CL
11.4
(37.4)
120
200
(61)
0.095
(0.312)
240
400
(122)
0.0485
(0.156)
***Based on 10% power drop.
For recommended temperature controller, see 4012-01145
(G.P. areas) and 4012-01147 (Hazardous locations).
Ground Fault Equipment Protection Devices (GFEPDs):
The IEEE standard (515-1989) for heating cables requires
the use of GFEPDs with a nominal 30 milliampere trip
level for “piping systems in classifed areas, those areas
requiring a high degree of maintenance, or which may be
exposed to physical abuse or corrosive atmospheres.”
Approvals:
Ordinary Locations
FM – Factory Mutual Approved
Hazardous (Classifed) Locations
FM – Factory Mutual Approved
Class I, Division 2, Groups B, C and D
Class II, Division 2, Groups F and G
Class III, Division 1 and 2
Electrical Specifcations:
For performance characteristics see next
page.