a
Ozone Resistance
Hose shall show no visible signs of cracking to the lin-
ing or cover when tested in accordance to ASTM D518
Procedure B, 100pphm/118°F/70 hours.
a
Chemical Resistance
Exposure to sea water and contamination by most chem-
ical substances, hydrocarbons, oils, alkalis, acids and
greases must have no effect on the short or long term per-
formance of the hose. A chemical resistance chart is avail-
able and Key Fire Hose will supply specific chemical resist-
ance data on request of purchaser for unique applications.
a
Heat Resistance
The hose, when subjected to a static pressure of 100 PSI,
shall be capable of withstanding a surface temperature of
1200°F for a minimum of two minutes without rupture
or damage to the synthetic reinforcement.
a
Hose Weight and Coil Diameters
The hose shall conform to the following average weights
and diameters
Part
Weight
Coil Size
Number
Diameter
per foot
Uncoupled
uncoupled
100’ Lengths
RC40-500
4”
.74 lbs
24”
RC50-400
5”
1.04 lbs
27”
RC60-300
6”
1.35 lbs
34”
a
Color
The color shall be of HI-VISIBILITY yellow or red.
Other colors available upon request.
a
Couplings
As required by purchaser, expansion ring threaded,
STORZ clamp ring, etc.
Key reserves the right to modify any specification with-
out prior notice to meet or exceed changing standards.
Customers are advised that special diameters or con-
struction characteristics can be produced on special
request and you are requested to contact Key Fire Hose
Corp. Miami, Florida.
PHONE 1-800-447-5666 • FAX 1-800-447-5664 • E-MAIL sales@keyfire.com
03/03
a
Hose Construction
Hose shall be made from 100 percent high tenacity synthetic
yarn, circularly woven and completely protected and locked-in
by tough highly resistant synthetic nitrile rubber, forming a sin-
gle homogeneous construction without the use of glues or
adhesives of any type. Meeting all requirements of NFPA 1961.
Warranty:
Hose shall carry a
five year
written warranty.
a
Lining Properties
Ultimate Tensile Strength:
Tensile strength of the lining and cover shall not be less
than 1750 PSI.
Ultimate Elongation:
500 percent minimum.
Accelerated Aging Test:
The tensile strength and ultimate elongation of the vul-
canized rubber compound which has been subjected to
the action of oxygen at a pressure of 300 PSI (±10 PSI)
and a temperature of 158°(±18°F) for a period of 96 hours
shall retain 60 percent of its originally stated properties.
a
Hydrostatic Pressure Tests
Part
Service Test
Acceptance Burst
Diameter
Number
Pressure Test Pressure Pressure
RC40-500
4”
250psi
500psi
750psi
RC50-400
5”
200psi
400psi
600psi
RC60-300
6”
150psi
300psi
500psi
a
Abrasion Resistance
Hose shall withstand 30,000 cycles on the Taber Abrasion
Machine (H-22 Wheel: 1 kg). Key Fire Hose Corporation on
request will supply written warranties that PRO-FLOW hose
meets a minimum 30,000 cycles. Other abrasion test results
(UL, DIN, etc.) can be supplied on request of purchaser
a
Cold Resistance
Hose shall have a capability of use down to -35°F. Hose shall
have no apparent damage to cover, reinforcement or lining
when subjected to the following cold bending test: a 50 ft.
length of dry hose is to be firmly coiled and placed in a cold box
at -35°F for a duration of 24 hours. Immediately after removal
of the hose from the box, hose should be uncoiled and laid out
by one operator. Following this procedure, the hose shall not
leak nor show any damage to the reinforcement when sub-
jected to the hydrostatic acceptance test stated above.
• Rubber Covered Hose
• 4”, 5”, and 6”
Visit us on the Web: www.keyfire.com
KF-031