Valves & Accessories
Introduction
Couplings
Outlets
Fittings
Val
ves &
Accesso
ries
High
Pressure
Advanced Copper
Method (IPS)
DI-LOK
®
Nipples
Plain-End
Fittings
HDPE
Couplings
Sock-It
®
Fittings
Stainless
Steel Method
Roll
Groovers
Installation
& Assembly
Special
Coatings
Design
Services
Technical
Data
Master Format
3 Part Specs.
Pictorial
Index
CTS Copper
System
www.anvilintl.com
81
FLOW DATA - FRICTION LOSS (FT. OF PIPE)
Valve Size
O.D.
C=100
C=120
Sch. 10
Sch. 30
Sch. 40
Sch. 10
Sch. 30
Sch. 40
In./mm
In./mm
Ft./m
Ft./m
Ft./m
Ft./m
Ft./m
Ft./m
2
2.375
10
—
8
14
— 11
50
60.3
3.0
—
2.4
4.3
—
3.4
2
1
/
2
2.875
14
— 10
20
— 15
65
73.0
4.3
—
3.0
6.1
—
4.6
3
3.500
17
— 12
23
— 17
80
88.9
5.2
—
3.7
7.0
—
5.2
4
4.500
17
— 13
23
— 18
100
114.3
5.2
—
4.0
7.0
—
5.5
5
5.563
14
— 11
20
— 15
125
141.3
4.3
—
3.4
6.1
—
4.6
6
6.625
23
— 19
33
— 26
150
168.3
7.0
—
5.8
10.1
—
7.9
8
8.625
35
32
30
50
45
43
200
219.1
10.7
9.8
9.1
15.2
13.7
13.1
10
10.750
28
25
24
40
36
34
250
273.1
8.5
7.6
7.3
12.2
11.0
10.4
12
12.750
31
28
26
44
39
37
300
323.9
9.4
8.5
7.9
13.4
11.9
11.3
SERIES 7800
Check Valves
For use in Grooved-End Piping Systems
FLOW DATA:
The approximate friction
losses, based on the Hazen and
Williams formula, expressed
in equivalent length of pipe is
given below. The friction losses
have been calculated on the
basis of fow rates typically
used with each size valve.
IMPORTANT NOTE:
Check valve life may be shortened and system damage may occur if check valves are installed too close to a source of unstable fow.
Check valves must be installed at a reasonable distance away from pumps, elbows, expanders, reducers or other similar devices.
Sound piping practices dictate a minimum of fve (5) times the pipe diameter for general use. Distances between three (3) and fve
(5) diameters are allowable provided the fow velocity is less than 8 feet per second. Distances less than 3 diameters are not recommended.
This valve may be installed vertically or horizontally. In a horizontal installation, the hinge pin is to be located on top.
Not for use in copper systems.
100
200
300 400 500
700
1000
2000
3000 4000 5000 7000 10000
1.0
1.5
0.9
0.8
0.7
0.6
0.5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
1.0
1.5
0.9
0.8
0.7
0.6
0.5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI)
NOMINAL PRE
SSURE DROP IN POUNDS PER SQUARE INCH (PSI)
FLOW RATE IN GALLONS PER MINUTE (GPM)
Friction Loss Series 7800 Check Valve (Water at 65°F)
2" Valve
2 1/2" Valve
3" Valve
4" Valve
5" Valve
6" Valve
8" Valve
12" Valve
10" Valve
GL-2.10