Master format 3 part specification
www.anvilintl.com
218
SECTION 15300
(CONT.)
Pipes, Valves and Fittings for Fire Protection Systems
C. Center sprinkler heads in ceiling tile and provide piping offsets as required.
D. Where ceiling is to be painted or sprayed, apply paper cover over sprinkler heads to ensure the head and escutcheons do not get coated.
Remove protective paper cover after painting or spraying is completed.
E. Provide mountable metal box of spare heads with proper wrench for head replacement.
3.6 TESTS AND INSPECTIONS
A. Contractor shall be responsible for testing and certifcation of systems and ordering inspections as required by authorities having jurisdiction.
B. All tests shall be conducted in the presence of and to the satisfaction of the Owner or an authorized representative.
C. Inspections shall be made by the Owner's authorized representative and inspectors having jurisdiction.
3.7 PROTECTION
A. After all tests have been made and the systems pronounced to be satisfactory, the Contractor shall go over all work and clean equipment,
fxtures, and related appurtenances and piping, and leave them clean and in complete working order at fnal completion of the project.
B. Protect installed products until completion of project.
C. Touch-up, repair or replace damaged products before Substantial Completion.
END OF SECTION
SECTION 15400
Pipes, Valves and Fittings for Plumbing Systems
Part 1 general
1.1 SECTION INCLUDES
A. Plumbing requirements.
1.2 RELATED SECTIONS
A. Section 07840 - Firestopping.
B. Section 08310 - Access Doors and Panels.
C. Section 15050 - Basic Mechanical Methods and Materials.
D. Section 15060 - Hangers and Supports.
E. Section 15500 - Piping Specialties.
1.3 RELATED SECTIONS
A. Manufacturers Standardization Society of the Valve and Fittings Industry (MSS) SP-127 Bracing for Piping Systems Seismic-Wind-Dynamic
Design, Selection, Application.
1.4 SYSTEM DESCRIPTION
A. Grooved products for steel and copper plumbing systems shall be used. Refer to Section 15050 - Basic Materials and Methods and Section
15500 - Piping Specialties for related materials.
1. Galvanized fttings to be used with galvanized pipe.
2. Schedule 10 Type 304 or 316 grooved stainless steel pipe and grooved stainless steel fttings shall be used in conjunction with copper
systems 8 inch (203 mm) diameter and above.
3. Couplings shall not be galvanized unless system is exposed to a corrosive environment.
4. Copper fttings shall be 99.9 percent lead free.
B. Contractor Design Requirements:
1. Incorporate in construction pipe hangers and supports to manufacturer's recommendations utilizing manufacturer's regular production
components, parts and assemblies.
1.5 SUBMITTALS
A. Submit under provisions of Section 01300.
B. [ Product Data ]: Manufacturer's data sheets on each product to be used, including:
1. Preparation instructions and recommendations.
2. Installation methods.