Master format 3 part specification
www.anvilintl.com
214
SECTION 15050
(CONT.)
Basic Mechanical Methods and Materials
B. Globe Valves - Model GBV-S (Soldered), GBV-T (Threaded), Balancing Valves - Model GBV-G (Grooved-End Straight), GBV-A (Grooved-End Angle):
1. To ensure accuracy of measurement of GBV-S, GBV-T, GBV-G and GBV-A valves, locate valves at least 5 pipe diameters downstream from
any ftting and at least 10 pipe diameters downstream from a pump.
2. Install no fttings within 2 pipe diameters downstream of valve.
3. Install valves with fow in the direction of the arrow on the valve body.
4. Provide easy access to probe metering ports (PMPs), drain ports and handwheel.
5. For solder applications, solder valve body in line using 95/5 solder.
6. Install valve-bonnet assembly into body, making sure non-asbestos gasket is in place.
7. Install valves in horizontal or vertical piping as indicated.
8. Do not install metering ports below the pipe (pointing down), as this will allow system sediment to accumulate in the ports.
9. Metering ports and body/drain plugs may be interchanged for improved accessibility.
END OF SECTION
SECTION 15300
Pipes, Valves and Fittings for Fire Protection Systems
Part 1 general
1.1 SECTION INCLUDES
A. Scope of work:
1. All areas as indicated on the drawings are to be protected by an automatic suppression system, of type as indicated.
2. Wet pipe.
3. Dry-pipe.
4. Wet standpipe.
5. Dry-standpipe.
B. Contractor shall be responsible for designing the distribution systems and sizing of the systems by hydraulic calculation; and shall provide the
necessary engineering drawings and calculations to obtain acceptance of all authorities having jurisdiction.
1.2 SECTION INCLUDES
A. Section 07840 - Firestopping.
B. Section 08310 - Access Doors and Panels.
C. Section 15050 - Basic Mechanical Methods and Materials.
D. Section 15060 - Hangers and Supports.
E. Section 15500 - Piping Specialties.
1.3 REFERENCES
A. ASTM International (ASTM) A536 - Standard Specifcation for Ductile Iron Castings.
B. Manufacturers Standardization Society of the Valve and Fittings Industry (MSS) SP-127 Bracing for Piping Systems Seismic-Wind-Dynamic
Design, Selection, Application.
C. NFPA 13 - Installation of sprinkler systems.
D. NFPA 72 - Installation, maintenance and use of protective signaling devices.
1.4 SYSTEM DESCRIPTION
A. System components to be UL listed/FM approved and labeled.
B. System components to be to be rated for minimum operating pressure of 175 psig.
C. Pipe, Valves, and Fittings - Grooved products for steel and copper fre protection systems shall be used. Refer to Section 15050 - Basic Materials
and Methods and Section 15500 - Piping Specialties.
D. Products shall be UL/ULC listed and FM approved. Materials shall be installed in accordance with current NFPA Standards, local Rating Bureau
and/or local Fire Marshall requirements.
GL-2.10