technical data
Introduction
Couplings
Outlets
Fittings
Val
ves &
Accesso
ries
High
Pressure
Advanced Copper
Method (IPS)
DI-LOK
®
Nipples
Plain-End
Fittings
HDPE
Couplings
Sock-It
®
Fittings
Stainless
Steel Method
Roll
Groovers
Installation
& Assembly
Special
Coatings
Design
Services
Technical
Data
Master Format
3 Part Specs.
Pictorial
Index
CTS Copper
System
www.anvilintl.com
207
T
B
D
C
OD
Flare
A
Gruvlok CTS Copper System – Roll Groove Specifications
-1-
-2-
-3-
-4-
-5-
-6-
-7-
-8-
Nominal
Size
Tubing Outside Diameter
Gasket Seat “A”
+/– 0.03 in.
+/– 0.76mm
Groove Width “B”
+0.03/–0.00 in.
+0.76/–0.00mm
Groove Diameter “C”
Nominal
Groove Depth
“D”
Min.
Wall
“T”
Max.
Flare
Diam.
Actual
Tolerance
Actual
Tolerance
+0.000
In.
In./mm
+ In./mm – In./mm
In./mm
In./mm
In./mm
– In./mm
In./mm
In./mm
In./mm
2
2.125
0.002
0.002
0.610
0.300
2.029
-0.020
0.048
0.058
2.220
54.0
0.05
0.05
15.5
7.6
51.54
-0.51
1.2
1.6
56.4
2
1
/
2
2.625
0.002
0.002
0.610
0.300
2.525
-0.020
0.050
0.065
2.720
66.7
0.05
0.05
15.5
7.6
64.14
-0.51
1.3
1.7
69.1
3
3.125
0.002
0.002
0.610
0.300
3.025
-0.020
0.050
DWV
3.220
79.4
0.05
0.05
15.5
7.6
76.84
-0.51
1.3
81.8
4
4.125
0.002
0.002
0.610
0.300
4.019
-0.020
0.053
DWV
4.220
104.8
0.05
0.05
15.5
7.6
102.08
-0.51
1.3
107.2
5
5.125
0.002
0.002
0.610
0.300
4.999
-0.020
0.053
DWV
5.220
130.2
0.05
0.05
15.5
7.6
126.97
-0.51
1.3
132.6
6
6.125
0.002
0.002
0.610
0.300
5.999
-0.020
0.063
DWV
6.220
155.6
0.05
0.05
15.5
7.6
152.37
-0.51
1.6
158.0
8
8.125
0.002
0.004
0.610
0.300
7.959
-0.020
0.083
DWV
8.220
206.4
0.05
0.10
15.5
7.6
202.16
-0.51
2.1
208.8
Column 1
Nominal tubing size ASTM B88
Column 2
Outsize diameter of copper tubing per ASTM B88. Allowable tolerance
from square cut ends is 0.030"/0.76mm for sizes 2"-3"; 0.045"/1.14mm for
sizes 4-8"
Column 3
Gasket seat must be free from scores, roll marks, indentations, grease and
dirt which may interfere with gasket sealing.
Column 4
Groove width is to be free from chips, dirt, etc. which may interfere with
proper coupling assembly.
Column 5
Groove diameter must be of uniform depth for the entire circumference
of the tubing. See column 6.
Column 6
Groove depth is for reference only; the groove diameter must conform to
column 5.
Column 7
DWV (Drain, Waste and Vent Piping) per ASTM B306.
Column 8
Maximum fare diameter is the OD at the most extreme tubing diameter.
GRUVLOK CTS COPPER SYSTEM
Roll Groove Specifcations
GL-2.10